3516B (60 Hz) with Upgradeable Package
At a Glance
Standby Rating
2250 ekW
|
Prime Power Rating
1825 ekW
|
Emissions/Fuel Strategy
Low fuel, Low Emissions
|
Voltage
380 to 480 Volts
|
Request a Quote
Overview
The3516B with the upgradeable packaging design has been developed for a wide range of applications, from emergency standby installations such as healthcare and datacenters to continuously powering remote installations. The packages can be optimized for performance to matters to you with either low emissions or low fuel consumption versions available. Backed by the worldwide network of Cat dealers ready to support your operation with technical support, service, parts, and warranty, Cat generator sets will provide the reliability and durability you expect.
Generator Set Specifications
+
-
Standby Rating |
2250 ekW |
Prime Power Rating |
1825 ekW |
Emissions/Fuel Strategy |
Low fuel, Low Emissions |
Voltage |
380 to 480 Volts |
Frequency |
60 Hz |
Speed |
1800 rpm |
Duty Cycle |
Standby, Mission Critical, Prime, Continuous |
Maximum Rating |
2250 ekW |
Minimum Rating |
1640 ekW |
Engine Specifications
+
-
Engine Model |
3516B TA, V-16, 4-Stroke Water-Cooled Diesel |
Bore |
6.69in |
Stroke |
7.48in |
Displacement |
4210.64in |
Compression Ratio |
14.0:1 |
Aspiration |
TA |
Fuel System |
MEUI |
Governor Type |
ADEM™ A4 |
Generator Set Dimensions
+
-
Length - Maximum |
234.5in |
Width - Maximum |
90in |
Height - Maximum |
98.2in |
Dry Weight - Genset (maximum) |
30310lb |
Standard Equipment:
Air Inlet System
+
-
-
Air cleaner; single element canister type
Control Panels
+
-
-
PLC functionality
-
Oil pressure (psi, kPa or bar)
-
Text alarm/event descriptions
-
KVAR/PF modes
-
Cat connect
-
Overspeed
-
Amps (per phase & average)
-
Programmable protective relaying functions:
-
DC volts
-
EMCP 4.2B
-
Power factor (per phase & average)
-
Reverse reactive power (kVAr) (32RV) - Overcurrent (50/51)
-
Load histogram feature
-
Generator set packages include:
-
Frequency (Hz)
-
Emergency stop pushbutton
-
Over/under voltage (27/59)
-
RFI suppression
-
24 Volt DC operation
-
Low coolant level
-
Reverse power (kW) (32) - Reverse reactive power (kVAr) (32RV) - Overcurrent (50/51)
-
4 Programmable relay outputs (Form A)
-
Volts (L-L & L-N)
-
Caterpillar's voltage regulator
-
IVR includes:
-
Auto/start/stop control
-
kVA (per phase, average & percent)
-
Lamp test
-
Over/under frequency (81 o/u)
-
Environmental sealed front face
-
3 Phase voltage sensing
-
Engine cool
-
kVAr-hr (total)
-
Low oil pressure
-
Accessory module data link
-
Emergency stop
-
Customer data link (Modbus RTU)
-
Communications:
-
Warning/shutdown with common LED indication of shutdowns for:
-
0 True RMS AC metering, 3-phase, +/-2% accuracy
-
Digital indication for:
-
Customizable screens
-
Failure to start (overcrank)
-
Serial annunciator module data link
-
Coolant temperature
-
Controls:
-
Overcurrent (50/51)
-
Number of I/O varies on options selected
-
Reactive droop capability
-
Low coolant temperature
-
High coolant temperature
-
Min / max exciter
-
Alarm acknowledge
-
RPM
-
Generator phase sequence
-
Limiter and exciter diode monitor
-
Speed adjust
-
Operating hours
-
kW (per phase, average & percent)
-
3 Analog inputs
-
Generator mounted - rear facing
-
6 Customer programmable digital inputs
Lubrication System
+
-
-
Oil filter, filler and dipstick
-
Oil drain lines and valve
-
Gear type lube oil pump
-
Fumes disposal
-
Lubricating oil
Mounting System
+
-
-
Rubber anti-vibration mounts - shipped loose
-
Rails - engine/generator/radiator mounting
-
Anti-vibration mounts (shipped loose)
Starting System
+
-
-
45 Amp Charging alternator
-
24 Volt electric starting motor
-
Battery and battery rack w/cables
-
Battery disconnect switch
Literature
+
-
-
Parts book
-
Operation & Maintenance Manual
Optional Equipment:
Air Inlet System
+
-
Dual element air cleaner
Single element filter
Cooling System
+
-
Water level switch gauges
Optional installed ATAAC radiators
Standard ambient ATAAC radiators
Standard ambient radiators
Coolant
Optional installed radiators
Crankcase System
+
-
Explosion relief valves
No explosion relief valves
Ventilation system
Exhaust System
+
-
Elbows
Flange and exhaust expanders
Tier 4 clean emissions module
Tier 4 clean emission MOD Kits
Clean emission parts
Exhaust offset
Mufflers
Tier 4 dosing cabinet
Flanges
Flexible fittings
Y Adapters
Fuel System
+
-
Fuel priming pumps (Tier 4) - Manual or electric
Primary fuel filter
General
+
-
US aid emblem
Special paint (Colors other than Caterpillar yellow or high performance paints)
Generators And Attachments
+
-
Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
Generator conversion
Differential current transformers (DCT)
Differential current transformers (DCT) 8.7 kV and 15 kV classes
Low / Medium voltage: 380, 440, 480, 600 volts, 3 phase 1800 rpm. RW, IE, No. of Leads = 6, Pitch = .6667: 1600 Frame
Low / Medium voltage: 380/400/415 volts, 3 phase 1500 rpm. RW, PM, No. of Leads = 6, Pitch = .6667: 1600 and 1800 Frames
Thermostat for space heater
Space heater
High voltage: 6300, 6600, 6900 volts, 3 phase 1800 rpm, FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
Alternator air cleaner
High voltage: 12470, 13200, 13800 volts, 3 phase 1800 rpm,FW, PM, No. of Leads = 6, Pitch = .6667: 2700, 3000 Frame
Low / Medium voltage: 380, 416, 440, 480, 600, 2400, 4160 Volts, 3 Phase 1800 RPM, FW, PM, No. of Leads = 6, Pitch = .6667: 1600, 1800 Frame
Instrumentation
+
-
Pyrometer and Thermocouples
Lubrication System
+
-
Oil level regulator
Prelube pumps
Lube oil in standard sump
Mounting System
+
-
Puck style low efficiency isolators
Spring type vibration isolators
IBC vibration isolators
Power Connections
+
-
Right side power connections
Ground cables between generator and terminal box
Neutral ground connections
Low voltage Circuit breakers
2700 Frame, four lead, four terminal
Rear power connections
Left side power connections
Center post busbars
Special Tests / Reports
+
-
PGS Test report @ 0.8 power factor
PGS Test report @ 1.0 power factor
Fuel consumption test
Canadian Standards Association certification
Torsional vibration analysis reports
IBC Certification
Generator test report
Generator set fuel consumption test
OSHPD Certification
Standard engine test charge
Starting And Charging
+
-
Engine barring device
Air pressure regulator
Starter cover
Electric starting motors
Jacket water heaters
Air starting motors
24 Volt battery set - Dry
10, 20, 35 and 50 Amp Battery chargers
Extended Service Coverage
+
-
Platinum, Gold and Silver coverage