XQ330 Tier 4 Final (264 ekW, 330 kVA)
At a Glance
Rating Prime
264 eKW (330 kVA)
|
Frequency
50/60 Hz
|
Voltage
120 - 600 V
|
Rating Standby
288 ekW (360 kVA)
|
Request a Quote
Overview
Generator Set
+
-
Rating Prime |
264 eKW (330 kVA) |
Frequency |
50/60 Hz |
Voltage |
120 - 600 V |
Rating Standby |
288 ekW (360 kVA) |
Dimensions
+
-
Height - Without Trailer |
78.5in |
Length - Without Trailer |
162.2in |
Width - Without Trailer |
92.8in |
Weight with Lube Oil and Coolant, Without Trailer |
10405lb |
Fuel Consumption
+
-
100% Load 60 Hz |
18.5gal/hr |
75% Load 60 Hz |
13.7gal/hr |
50% Load 60Hz |
9.8gal/hr |
100% Load 50 Hz |
16.5gal/hr |
75% Load 50 Hz |
12.5gal/hr |
Noise rating (with enclosure)
+
-
Sound Power @ 7 meters (23 feet) @ Prime Rating |
70.2 dB(A) (60Hz) |
Standard Equipment:
Cat C9.3b Diesel Engine
+
-
-
Heavy-duty.
Turbocharged.
After treatment
Control Panel
+
-
-
Digital EMCP4.4 set mounted controller
Cat Connect Remote Monitoring
+
-
-
Provides package monitoring and management
Cooling System
+
-
-
Package mounted radiator with vertical air discharge.
Filled from factory
Charging / Starting System
+
-
-
Single 24V electric starting motor
Fuel System
+
-
-
24 hour dual wall fuel tank
Air Filter
+
-
-
Efficient air cleaner with service indicator
Distribution
+
-
-
Single, robust enclosure for controls and distribution c/w 3 pole 1000A maim circuit breaker and safety cut off
Structure
+
-
-
Heavy Duty steel base frame with integral fuel tank.
Dual Point Lifting frame and 4 point lift.
base frame is wider than enclosure to protect generator set during transportation
Enclosure
+
-
-
Sound attenuating, galvanised steel enclosure with exceptional noise reduction performance
Exhaust
+
-
-
Integrated spark arresting silencer
Lube Oil
+
-
-
On engine primary and secondary oil filters. Filled from factory 500-hour oil change interval
General
+
-
-
Factory tested and inspected
Optional Equipment: