Engine Paralleling and Integration Control (EPIC)
At a Glance
Configuration
Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control)
|
Modes of Operation
Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel)
|
Application
LV and MV (208V-27kV)
|
ANSI Protective Devices
15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade)
|
Request a Quote
Overview
The Engine Paralleling and Integration Control (EPIC) product line provides standard paralleling controls in a remote cabinet separate from the engine generator set and separate from switchgear (breakers and bus).
Technical Summary
+
-
Configuration |
Remote modular paralleling control system (Master Control Panel for the first 2 generator sets and optional tie breaker, separate add-on control panels for up to 8 additional generator sets, utility paralleling control, and distribution control) |
Modes of Operation |
Emergency Standby with redundant master control, Utility paralleling, peak shaving, and closed transition to/from Generator Power (with optional utility control panel) |
Application |
LV and MV (208V-27kV) |
Generator Protective Devices
+
-
ANSI Protective Devices |
15/25. 27/59, 81 O/U, 32, 40, 90 (Industrial Grade) |
Utility Protective Devices
+
-
ANSI Protective Devices |
15/25. 27/59, 81 O/U, 32,47 (Industrial Grade) |
Environmental Parameters
+
-
Certifications |
UL / cUL 508A |
Control Panel Enclosure |
NEMA 12 |
Operating Temperature |
0°C to 55°C |
Storage Temperature |
-20°C to 60°C |
Standard Equipment:
Instant Auto Selector Switch
+
-
-
Allows user to return sysem to automatic in the event of a touchscreen failure
Optional Equipment:
Generator Control Panel (for 3-10 Gensets)
+
-
With breaker position indications and circuit breaker control switch
Utility Control Panel (for Utility Paralleling And Control)
+
-
With utility close lockout switch, breaker position indications, and circuit breaker control switch
Supplemental Hardware 25 Device
+
-
Provides additional discrete synchronization protection
Data Table Interface
+
-
Accommodates interface with a building management system
Generator Demand Priority Control
+
-
An automatic priority sequencing function to modulate the number of gensets online to control load percentages per machine, assist with fuel efficiency, and maintain adequate reserve capacity