3412C | 750kVA 50Hz Generator Set
At a Glance
Maximum Rating
680 kVA
|
Minimum Rating
680 kVA
|
Emissions/Fuel Strategy
Low Fuel Consumption
|
Voltage
380 to 415 Volts
|
Request a Quote
Overview
Generator Set Specifications
+
-
Maximum Rating |
680 kVA |
Minimum Rating |
680 kVA |
Emissions/Fuel Strategy |
Low Fuel Consumption |
Voltage |
380 to 415 Volts |
Frequency |
50 Hz |
Speed |
1500 rpm |
Duty Cycle |
Standby, Prime |
Engine Specifications
+
-
Engine Model |
3412C TA, V-12, 4-Stroke Water-Cooled Diesel |
Bore |
5.4in |
Stroke |
6in |
Displacement |
1648.86in³ |
Compression Ratio |
13:01 |
Aspiration |
Turbocharged, Air to Air Aftercooled |
Fuel System |
Pump and Lines |
Governor Type |
ADEM™ A5 |
Generator Set Dimensions
+
-
Length - Maximum |
162.4in |
Width - Minimum |
75in |
Width - Maximum |
78.3in |
Height - Maximum |
75in |
Dry Weight - Genset (minimum) |
12039lb |
Dry Weight - Genset (maximum) |
13030lb |
Standard Equipment:
Air Inlet System
+
-
-
Air cleaner, single element canister type with service indicator
Control Panel
+
-
-
GCCP Control panel
-
Over/under voltage (27 / 59)
-
Environmental sealed front face
-
Generator phase sequence
-
Communications
-
Digital I/O module
-
Features include:
-
2 Programmable relay outputs (Form C)
-
Compatible with the following optional modules:
-
Customer data link (Modbus RTU)
-
4 programmable relay outputs (Form A)
-
Amps (per phase & average)
-
kVA (per phase, average & percent)
-
Text alarm/event descriptions
-
Low coolant level
-
Generator temperature monitoring module
-
Run/auto/ stop/control
-
Overspeed
-
Serial annunciator module data link
-
Emergency stop pushbutton
-
Frequency (Hz)
-
RPM
-
6 programmable digital inputs
-
Oil pressure (psi, kPa or bar)
-
Engine cycle crank
-
Operating hours
-
Local annunciator
-
coolant temperature
-
kW-hr (total)
-
Programmable protective relaying functions:
-
kW (per phase, average & percent)
-
Low oil pressure
-
Reverse power (kW) (32)
-
Remote Serial annunciator
-
DC volts
-
Power factor (per phase & average)
-
Remote CAN annunciator
-
24 Volt DC operation
-
Accessory module data link
-
Failure to start (overcrank)
-
Over/under frequency (81 o/u)
-
kVAr (per phase, average & percent)
-
Warning/shutdown with common LED indication of shutdowns for:
-
Low coolant temperature
-
2 Programmable digital outputs
-
Reverse reactive power (kVAr) (32RV)
-
Emergency stop
-
Digital indication for:
-
High coolant temperature
-
Speed adjust
-
Voltage adjust
-
Volts (L-L & L-N)
-
Overcurrent (50 / 51)
Cooling System
+
-
-
Fan and belt guards
-
Coolant drain line with valve, piped to edge of base
-
Caterpillar extended life coolant
-
Coolant level shutdown
-
Radiator with guard (Sized for 50 degrees C)
Exhaust System
+
-
-
Stainless steel exhaust flex with ANSI style outlet flange, gasket, bolts and mating weld flange, shipped loose
Fuel System
+
-
-
Flexible fuel lines terminated on base
-
Fuel priming pump
-
Primary and Secondary fuel filters
-
Water seperator
Generator And Attachments
+
-
-
3-phase sensing
-
SR4B self excited
-
Class H insulation
-
2:1 Volts/Hz
-
Reactive droop
-
VR6 voltage regulator
-
Busbar termination
-
Class F temperature rise
-
12 Leads
Lube System
+
-
-
Oil drain line with valve, piped to edge of base
-
Lubricating oil
-
Oil filter
-
Fumes disposal, piped to front of radiator
Mounting System
+
-
-
Base, formed steel with linear vibration isolators between base and engine-generator
Starting / Charging System
+
-
-
Battery with rack, cables
-
45 amp Charging alternator
-
24 volt starting motor
-
Fuel shutoff solenoid
Optional Equipment:
Air Inlet System
+
-
Open element air cleaners
Heavy duty air cleaners
Dual element air cleaners
Circuit Breakers
+
-
1600 Amp, 3 pole, Non-UL, 100% rated, 24 volt DC shunt trip
1250, 1600 Amp, 3 pole, IEC 100% rated, 24 volt DC shunt trip
Control Panel
+
-
First local annunicators
Local discrete I/O package
Generator temperature monitoring package
Ground fault relay
Remote custom annunicator
GCCP Control panel
Generator running VFC
GCCP Control panel
Vandal proof panel door
Common alarm/shutdown relay
Cooling System
+
-
Jacket water heaters
Radiator duct flange
European Certifications
+
-
Eurasian Conformity (EAC) mark
Exhaust System
+
-
Elbow kit
Manifold and turbocharger guards
Through wall installation kit
Mufflers
Generator And Attachments
+
-
Digital voltage regulator
Oversize and premium generators
Space heater
Permanent magnet excitation (PMG)
Mounting System
+
-
Fuel tank base (1200 ltr)
Special Tests / Reports
+
-
PGS Test report @ 1.0 power factor
PGS Test report @ 0.8 power factor
Starting / Charging
+
-
Heavy duty starting system
Battery chargers
Battery disconnect switch
Oversize batteries