3512B (50 Hz) Generator Set
At a Glance
Standby Rating
1875/1750 kVA
|
Prime Power Rating
1700/1600 kVA
|
Emissions/Fuel Strategy
Low Fuel, Low Emissions
|
Voltage
380 to 415 Volts
|
Request a Quote
Overview
Generator Set Specifications
+
-
Standby Rating |
1875/1750 kVA |
Prime Power Rating |
1700/1600 kVA |
Emissions/Fuel Strategy |
Low Fuel, Low Emissions |
Voltage |
380 to 415 Volts |
Frequency |
50 Hz |
Speed |
1500 rpm |
Duty Cycle |
Standby, Mission Critical, Prime |
Maximum Rating |
1875 kVA |
Minimum Rating |
1600 kVA |
Engine Specifications
+
-
Engine Model |
3512B TA, V-12, 4-Stroke Water-Cooled Diesel |
Bore |
6.69in |
Stroke |
8.46in |
Displacement |
3576in³ |
Displacement - HD |
3576in³ |
Compression Ratio |
15.5:1 HD |
Aspiration |
TA |
Fuel System |
Electronic Unit Injection |
Governor Type |
ADEM™ A3 |
Stroke - HD |
8.46in |
Generator Set Dimensions
+
-
Length - Minimum |
206.6in |
Length - Maximum |
215.3in |
Width - Minimum |
77.8in |
Width - Maximum |
90in |
Height - Maximum |
93.2in |
Dry Weight - Genset (minimum) |
25010lb |
Dry Weight - Genset (maximum) |
26840lb |
Standard Equipment:
Air Inlet System
+
-
-
Aingle element canister type air cleaner with service indicator
Cooling
+
-
-
Package mounted radiator (except C175)
Control Panel
+
-
-
Speed adjust
-
Oil pressure (psi, kPa or bar)
-
4 Programmable relay outputs (Form A)
-
kVAr (per phase, average & percent)
-
Over/under frequency (81 o/u)
-
Operating hours
-
Accessory module data link
-
Text alarm/event descriptions
-
Amps (per phase & average)
-
DC volts
-
Frequency (Hz)
-
2 Programmable relay outputs (Form C)
-
kVAr-hr (total)
-
Volts (L-L & L-N)
-
RPM
-
kW (per phase, average & percent)
-
Over/under voltage (27 / 59)
-
Environmental sealed front face
-
Controls:
-
Engine cool-down timer
-
Customer data link (Modbus RTU)
-
High coolant temperature
-
2 Programmable digital outputs
-
Power factor (per phase & average)
-
24 Volt DC operation
-
Overspeed
-
Alarm acknowledge
-
Lamp test
-
kW-hr (total)
-
Low coolant temperature
-
Emergency stop
-
Generator phase sequence
-
Auto/start/stop control
-
Cat ECS 100
-
Low oil pressure
-
Engine cycle crank
-
Programmable protective relaying functions:
-
Reverse power (kW) (32)
-
Generator mounted - rear facing
-
Digital indication for:
-
Overcurrent (50 / 51)
-
Warning/shutdown with common LED indication of shutdowns for:
-
kVA (per phase, average & percent)
-
Serial annunciator module data link
-
Emergency stop button
-
Reverse reactive power (kVAr) (32RV)
-
6 Programmable digital inputs
-
Failure to start (overcrank)
-
Low coolant level
-
Communications
-
Coolant temperature
-
True RMS AC metering, 3 phase, +/-2% accuracy
Fuel
+
-
-
Primary fuel filter with integral water separator
-
Secondary fuel filters
-
Fuel priming pump
Control System
+
-
-
Failure to start (overcrank)
-
Auto/start/stop control
-
Cat ECS 100
-
Lamp test
-
Emergency stop pushbutton
-
4 programmable digital inputs
-
Volts (L-L & L-N)
-
Low coolant level
-
Overspeed
-
frequency (Hz)
-
Engine cycle crank
-
DC volts
-
Coolant temperature
-
Alarm acknowledge
-
True RMS AC metering, 3-phase, +/-2% accuracy
-
Communications
-
24 Volt DC operation
-
Engine cool-down timer
-
RPM
-
Warnings/shutdown indicators
-
Digital indication for:
-
Oil pressure
-
Low oil pressure
-
Amps (per phase & average)
-
Speed adjust
-
Emergency stop
-
4 programmable digital outputs
-
Operating hours
-
High coolant temperature
Generator
+
-
-
Matched to the performance and output characteristics of Cat engines
-
IP23 Protection
Generator System
+
-
-
Internal excitation (IE)
-
NEMA Class H insulation
-
Caterpillar's digital voltage
regulator (CDVR)
-
Class H temperature rise at 40C ambient
-
3-phase voltage sensing
-
Busbar connections
-
min/max exciter
-
Random wound
-
3 phase brushless, Salient pole
-
RFI suppression
-
Winding temperature detectors
-
6 Lead
Literature
+
-
-
Operation & Maintenance Manual
-
Parts book
Cooling System
+
-
-
Coolant drain line with valve
-
Radiator fan and fan drive
-
Fan and belt guards
-
JWAC
-
Caterpillar extended life coolant. (Not included with packages without radiator, installed SF44CTS, shipped loose radiators or heat exchangers)
-
Coolant level sensors (Not included with packages without radiator)
Exhaust System
+
-
-
Dry exhaust manifold
-
Flanged faced outlet(s)
Fuel System
+
-
-
Flexible fuel lines - shipped loose
-
Secondary fuel filters
-
Fuel priming pump
-
Fuel cooler; not included with packages without radiator
Generators And Attachments
+
-
-
6 Leads
-
Note: 1800 Frames are form wound, permanent magnet excitation (PMG), with winding temp detectors
-
Busbar connections, top center mounted, top cable entry
-
KVAR / PF modes
-
Internal excitation (IE)
-
Generator set packages include: Regulator (CDVR)
-
RFI suppression
-
Winding temperature detectors
-
NEMA Class H insulation
-
50 Hz models: IEC standard hole pattern
-
Reactive droop capability
-
3 Phase brushless, Salient pole
-
Exciter diode monitor
-
Min / max exciter limiter
-
Random wound
-
3 Phase voltage sensing
-
LV
-
Class H temperature rise at 40C ambient (125C prime / 150C standby)
-
Caterpillar's digital voltage regulator (CDVR) includes:
Governing System
+
-
-
Woodward 2301A isochronous governor
Lube System
+
-
-
Lubricating oil
-
Fumes disposal
-
Integral lube Oil cooler
-
Oil drain lines and valve
-
Gear type lube oil pump
-
Oil filter, filler and dipstick
Mounting System
+
-
-
Rubber anti-vibration mounts - shipped loose
-
Rails - Engine/generator/radiator mounting
Starting / Charging System
+
-
-
24 Volt electric starting motor
-
Battery and battery rack w/cables
-
Battery disconnect switch
General
+
-
-
Paint - Caterpillar yellow with high gloss black rails & radiator
-
RH service
-
SAE standard rotation
-
Flywheel and Flywheel housing-SAE No. 00
Optional Equipment:
Air Inlet System
+
-
Dual element air cleaners
Remote air inlet adaptors
Air inlet protection
Generator
+
-
Internal excitation (IE)
Anti-condensation heater
Oversize and premium generators
Permanent magnet excitation (PMG)
Circuit Breakers
+
-
Cable entry options
Optional busbar power connections
EMAX breakers connections
Center posts busbars
2000, 2500, 3200 and 4000 Amp, 3 pole, IEC rated Circuit breakers
Breaker harnesses
2000, 2500, 3200 and 4000 Amp, 4 pole, IEC rated Circuit breakers
Controls packaging - Enclosures
Busbar connections
EMAX Circuit breakers
Power Termination
+
-
Circuit breakers, UL listed
Circuit breakers, IEC compliant
Mounting
+
-
Rubber anti-vibration mounts
Spring type vibration isolators
IBC isolators
Control Panels
+
-
Annunciator modules
Generator temperature monitoring
Vandle proof panel door
Auxiliary boxes
Mounting group - External box clips
Ground (Automatically selected)
Remote speed adjust
Local PC monitoring
Customer connection mounting locations
EMCP 4.4
Governors
Customer interface options
Starting/charging
+
-
Oversize batteries
Air starting motor with control and silencer
Heavy duty starting system
Jacket water heater
Charging alternator
Battery chargers
Cooling System
+
-
Water level switch gauges
Heat exchangers
Optional radiator arrangements
European Certifications
+
-
European Directive genset, DoI (Declaration of Incorporation)
EU Declaration of Conformity
European Union certification
Eurasian Conformity (EAC) mark
Exhaust System
+
-
Through-wall installation kit
Mufflers
Muffler mounting kits
Flexible fittings
Generators And Attachments
+
-
Generator conversion
1500 RPM, 380/400/415volts @ 50 Hz, 3 phase, random wound, Permanent magnet excitation (PMG), No. of leads = 6, pitch= 0.6667
Space heater
1500 RPM, 380/400/415volts @ 50 Hz, 3 phase, Form wound, Permanent magnet excitation (PMG), No. of leads = 6, pitch= 0.6667
1500 RPM, 380/400/415volts @ 50 Hz, 3 phase, random wound, Internal excitation (IE), No. of leads = 6, pitch= 0.6667
Instrumentation
+
-
Pyrometer and thermocouples
Lube System
+
-
Oil level reg-1 shallow pan
Manual prelube sump pumps
Electric prelube pumps
Mounting System
+
-
IBC vibration isolators
Spring type vibration isolators
Special Tests / Reports
+
-
PGS Test report @ 0.80 power factor
PGS Test report @ 1.0 power factor
IBC seismic Certifications
Neutral ground-LV
Neutral grounding connection
Starting / Charging System
+
-
24 Volt dual electric starting motor
Oversize battery set
Jacket water heaters
Ether starting aid
20 Amp Battery charger
10 Amp Battery chargers