Generator Set Specifications
+ -Standby Rating | 2250 ekW |
Prime Power Rating | 1825 ekW |
Emissions/Fuel Strategy | Low Fuel, Low Emissions |
Voltage | 380 to 13800 Volts |
Frequency | 60 Hz |
Speed | 1800 rpm |
Duty Cycle | Standby, Mission Critical, Prime, Continuous |
Maximum Rating | 2250 ekW |
Minimum Rating | 1640 ekW |
Engine Specifications
+ -Engine Model | 3516B TA, V-16, 4-Stroke Water-Cooled Diesel |
Bore | 6.69in |
Stroke | 7.48in |
Displacement | 4210.64in |
Compression Ratio | 14.0:1 Std 15.5:1 HD |
Aspiration | TA |
Fuel System | Electronic unit injection |
Governor Type | Adem™3 |
Generator Set Dimensions
+ -Length - Maximum | 251.4in |
Width - Maximum | 90in |
Height - Maximum | 98.2in |
Dry Weight - Genset (maximum) | 31270lb |
Standard Equipment:
Air Inlet System
+ --
Air cleaner; single element canister type
Cooling
+ --
Package mounted radiator
Exhaust
+ --
Exhaust flange outlet
Fuel
+ --
Primary fuel filter with integral water separator
-
Secondary fuel filters
-
Fuel priming pump
Generator
+ --
IP23 Protection
-
Matched to the performance and output characteristics of Cat engines
Power Termination
+ --
Busbar
Control Panel
+ --
EMCP 4 Genset controller
General
+ --
Paint - Caterpillar yellow except rails and radiators gloss black
Control Panels
+ --
Speed adjust
-
Text alarm/event descriptions
-
Generator set packages include Caterpillar's voltage regulator
-
Auto/start/stop control
-
24 Volt DC operation
-
EMCP 4.2B
-
Generator mounted - Rear facing
-
Controls:
-
Environmental sealed front face
-
Engine cool-down timer
-
Emergency stop pushbutton
-
Limiter and exciter diode monitor
-
Engine cycle crank
-
Lamp test
-
Alarm acknowledge
-
Customizable screens
-
PLC functionality
-
Load histogram feature
-
0 True RMS AC metering, 3-phase, +/-2% accuracy
-
Operating hours
-
Digital indication for:
-
DC volts
-
RPM
-
Coolant temperature
-
Amps (per phase & average)
-
Oil pressure (psi, kPa or bar)
-
Volts (L-L & L-N)
-
Frequency (Hz)
-
Power factor (per phase & average)
-
kW (per phase, average & percent)
-
High coolant temperature
-
Low oil pressure
-
Warning/shutdown with common LED indication of shutdowns for01/10/2018:
-
kVAr (per phase, average & percent)
-
kVA (per phase, average & percent)
-
kVAr (per phase, average & percent)
-
Emergency stop
-
Overspeed
-
Failure to start (overcrank)
-
Programmable protective relaying functions:
-
Low coolant temperature
-
Generator phase sequence
-
Low coolant level
-
1 Programmable digital outputs
-
Gear type lube oil pump
-
Battery disconnect switch
-
Caterpillar yellow with high gloss black rails and radiator
-
NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby)
-
Medium voltage: Form wound - Permanent magnet excitation (PMG) - Winding temperature detectors - NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby) - Busbar connections, right side extension box, bottom cable entry - NEMA standard hole pattern
-
Fumes disposal
-
Permanent magnet excitation (PMG)
-
NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby)
-
Permanent magnet excitation (PMG)
-
NEMA standard hole pattern
-
Reverse reactive power (kVAr) (32RV)
-
Over/under voltage (27/59)
-
NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby)
-
Permanent magnet excitation (PMG)
-
Class H insulation, Class F temperature rise at 40C ambient (105C prime / 130C standby)
-
Permanent magnet excitation (PMG)
-
SAE standard rotation
-
Internal excitation (IE)
-
Flexible fuel lines - shipped loose
-
IVR includes reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, min / max exciter
-
Busbar connections, right side extension box, bottom cable entry
-
Medium voltage:
-
Communications:
-
NEMA standard hole pattern
-
Lubricating oil
-
Oil drain lines and valve
-
3 Phase brushless, Salient pole
-
24 Volt electric starting motor
-
6 Customer programmable digital inputs
-
Dry exhaust manifold
-
Accessory module data link
-
ADEM A3
-
Form wound
-
ATAAC - 3516E package radiators shipped installed
-
Busbar connections, top center mounted, top cable entry
-
High voltage:
-
4 Programmable relay outputs (Form A)
-
Anti-condensation space heater
-
NEMA Class H insulation system, Class H temperature rise at 40C ambient (125C prime / 150C standby)
-
Controls: Speed adjust - Auto/start/stop control - Engine cool-down timer - Engine cycle crank - Alarm acknowledge - Lamp test - Load histogram feature - PLC functionality - Customizable screens -0 True RMS AC metering, 3-phase, +/-2% accuracy
-
NEMA standard hole pattern
-
45 Amp Charging alternator
-
3 Analog inputs
-
Random wound
-
Anti-vibration mounts (shipped loose)
-
Cat connect
-
Oil filter, filler and dipstick
-
Rails - Engine/generator/radiator mounting
-
Customer data link (Modbus RTU)
-
Flywheel and flywheel housing - SAE No. 00
-
English
-
Busbar connections, right side extension box, bottom cable entry
-
Serial annunciator module data link
-
Integral lube oil cool
-
Certified standard PGS provided
-
Winding temperature detectors
-
1 Programmable relay outputs (Form C)
-
Reverse power (kW) (32)
-
Form wound - Permanent magnet excitation (PMG)
-
Right hand servicing
-
Overcurrent (50/51)
-
6 Lead
-
Flanged faced outlet(s)
-
Low voltage:
-
Number of I/O varies on options selected
-
Battery and battery rack w/cables
-
Over/under frequency (81 o/u)
-
Fuel cooler; not included with packages without radiator
-
Busbar connections, right side extension box, bottom cable entry
-
Rubber anti-vibration mounts - shipped loose
-
NEMA standard hole pattern
Optional Equipment:
Control System
+ -EMCP 4.3, EMCP 4.4
Air Inlet System
+ -Single element filter
Dual element air cleaner
Exhaust
+ -Exhaust mufflers
Generator
+ -Permanent magnet excitation (PMG)
Internal excitation (IE)
Anti-condensation heater
Oversize and premium generators
Cooling System
+ -Water level switch gauges
Standard ambient radiators
Coolant
Standard ambient ATAAC radiators
Optional installed ATAAC radiators
Air inlet protection including air shut off magnetic switch
Optional installed radiator
Power Termination
+ -Circuit breakers, IEC compliant
Circuit breakers, UL listed
Control Panels
+ -Generator temperature monitoring & protection
Remote monitoring software
Load share module
Digital I/O module
Exhaust System
+ -Exhaust Offset
Flanges
Elbows
Y Adapters
Flange and exhaust expanders
Clean emission parets
Mufflers
Flexible fittings
Fuel System
+ -Primary fuel filter
General
+ -Special paint
US aid emblem
Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
EEC Declaration of Conformity
Integral & sub-base fuel tanks
Enclosures: Sound attenuated, weather protective
Integral & sub-base UL listed dual wall fuel tanks
EU Certificate of Conformance (CE)
The following options are based on regional and product configuration:
Automatic transfer switches (ATS)
UL 2200 package
Mounting
+ -Rubber anti-vibration mounts
Spring type vibration isolators
IBC isolators
Generators And Attachments
+ -Generator conversions - IE and PM
380, 440, 480, 600 Volts, 3 phase, 1800 rpm, RW, PM, No. of leads: 6, Picth: 0.6667 - 1600 Frame
380, 440, 480, 600 Volts, 3 phase, 1800 rpm, RW, IE, No. of leads: 6, Picth: 0.6667 - 1600 Frame
380, 416, 440, 480, 600, 2400, 4160 Volts, 3 phase, 1800 rpm, RW, PM, No. of leads: 6, Picth: 0.6667 - 1600 and 1800 Frames
Alternator air cleaner
Space heater
Intrumentation
+ -Pyrometer and thermocouples
Lube System
+ -Prelube pump groups
Oil lever regulator
Lube oil
Starting/charging
+ -Battery chargers
Air starting motor with control and silencer
Heavy duty starting system
Oversize batteries
Charging alternator
Crankcase Systems
+ -Crankcase protection group: No explosion relief valves; Explosion relief valves
Crankcase ventilation system
Mounting System
+ -Spring type vibration isolators
IBC vibration isolators
Puck style low efficiency isolators
Power Connections
+ -Neutral ground connections
Center post busbarss
Right, left side and rear power connections
Grounding groups
Special Tests / Reports
+ -Standard engine test charge
IBC Certification
Special package tests: PGS Test report @ 1.0 and 0.8 power factors
Generator set test report
CSA Certification
Torsional vibration analysis TVA report
Fuel consumption test
Starting / Charging Sytem
+ -Jacket water heaters