C15 (50 Hz) China Non Road
At a Glance
Maximum Rating
550 kVA
|
Minimum Rating
365 kVA
|
Emissions/Fuel Strategy
Low Fuel, Tier 2 or 3
|
Voltage
208 to 600 Volts
|
Request a Quote
Overview
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Generator Set Specifications
+
-
Maximum Rating |
550 kVA |
Minimum Rating |
365 kVA |
Emissions/Fuel Strategy |
Low Fuel, Tier 2 or 3 |
Voltage |
208 to 600 Volts |
Frequency |
50 Hz |
Speed |
1500 rpm |
Duty Cycle |
Standby, Prime |
Engine Specifications
+
-
Engine Model |
C15 ATAAC, I-6, 4-Stroke Water-Cooled Diesel |
Bore |
5.4in |
Stroke |
6.75in |
Displacement |
927.56in³ |
Compression Ratio |
16.1:1 |
Aspiration |
Air to Air Aftercooled |
Fuel System |
MEUI |
Governor Type |
Adem™A4 |
Generator Set Dimensions
+
-
Length - Maximum |
222.7in |
Width - Maximum |
90in |
Height - Maximum |
93.2in |
Standard Equipment:
Air System
+
-
-
Aftercooler core
-
Turbocharger
-
Air cleaner - Non canister disposable paper filter
Cooling System
+
-
-
Radiator and cooling fan with guard
-
Coolant drain line with valve
-
Caterpillar extended life coolant
-
Fan drive, battery charging alternator drive
Fuel
+
-
-
Secondary fuel filters
-
Fuel priming pump
-
Primary fuel filter with integral water separator
Exhaust
+
-
-
Stainless steel exhaust flex, gaskets, raincap & SAE exhaust flange
for customer use - shipped loose
-
Exhaust flange outlet
Fuel System
+
-
-
Standard open set fuel tank/base supplied
-
Base, formed steel with single wall integral 8-hour fuel tank
Generator
+
-
-
IP23 Protection
-
Matched to the performance and output characteristics of Cat engines
-
Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
Generator And Attachments
+
-
-
IP23 Protection
-
A Frame generator - IP21 Protection
-
Segregated low voltage (AC/DC) wiring panel
-
Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
-
Optional LC Frame generator - IP23 Protection
-
Power center, IP22
-
Integrated voltage regulator (IVR)
Governing System
+
-
-
Cat electronic governor (ADEM A4)
Lube System
+
-
-
Lubricating oil
-
Oil drain valves
Mounting
+
-
-
Rubber vibration isolators
Mounting System
+
-
-
Rubber vibration isolators
Starting/charging
+
-
-
24 Volt battery with rack and cables
-
Batteries
-
24 volt starting motor
General
+
-
-
Engine and alternator pre paint, Caterpillar yellow
-
Paint - Caterpillar yellow except rails and radiators gloss black
Optional Equipment:
Air Inlet System
+
-
Single element air cleaner
Dual element air cleaner
Exhaust
+
-
Industrial, residential, critical mufflers
Certifications
+
-
EU Certificate of Conformance (CE)
Global certification for CIS
Generator
+
-
Oversize and premium generators
Anti-condensation heater
Excitation: [ ] Permanent magnet excitation (PMG) Excited (PM) [ ] Internally Excited (IE)
Power Termination
+
-
Circuit breakers, UL listed
Circuit breakers, IEC compliant
Circuit Breakers
+
-
4 Pole (IEC-100% rated) Circuit breakers - Motorised
3 Pole (IEC-100% rated) Circuit breakers - Motorised
Auxiliary contacts, circuit breaker
4 Pole (IEC-100% rated) Circuit breakers - Package mounted
Padlockable circuit breaker device
Power terminal strip
Shunt trip for IEC circuit breaker
3 Pole (IEC-100% rated) Circuit breakers - Package mounted
Control Panels
+
-
Protective devices: Earth fault relay ; Earth leakage Ground fault relay ; Overload shutdown via breaker ; Low fuel level alarm ; Low fuel level shutdown ; High fuel level alarm ; Fuel level sensor
Remote annunciator module
Oil temperature displays
GCCP 1.4
Local annunciator
Local alarm horn
Volt free contacts
Starting/charging
+
-
Jacket water heater
Heavy duty starting system
Battery chargers
Oversize batteries
Charging alternator
Cooling System
+
-
Radiator duct flange
Stone guards
Low coolant temperature alarm
Enclosures
+
-
Sound attenuated enclosures
High ambient sound attenuated enclosures
Exhaust System
+
-
End in/end out mufflers - 10, 25 and 35 dBA attenuation
Manifold and turbocharger guards
Flexible exhaust fittings
6 and 8 inch flange GP
6 and 8 inch elbow kit
Engine mounted muffler
Fuel System
+
-
Dual wall fuel tank base
Manual fuel transfer pump
Fuel transfer system controls
General
+
-
UL 2200 package
Automatic transfer switches (ATS)
Narrow, wide or skid base
Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
Single or dual wall sub-base fuel tanks
EU Certificate of Conformance (CE)
EEC Declaration of Conformity
The following options are based on regional and product configuration:
Single or dual wall integral fuel tanks
CSA Certification
Sound attenuated, weather protective or high ambient weather protective enclosure
Integral & sub-base UL listed dual wall fuel tanks
Generator And Attachments
+
-
Oversize A Frame generator
LC frame generator
Oversize LC frame generator
CIP A Frame generator
LC frame CIP generator
Permanent magnet excitation (PMG) generator
Space heaters
Ingress protection
Mounting System
+
-
Narrow skid base - replaces standard fuel tank base
Special Test / Reports
+
-
PGS Test report @ 1.0 power factor
PGS Test report @ 0.8 power factor
Starting / Charging System
+
-
5 Amp single Battery charger
Battery disconnect switch