C15 Generator Set
360° Exterior View
360° Exterior View
At a Glance
|
|
|
|
Overview
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Generator Set Specifications
+ -Maximum Rating | 500 ekW |
Minimum Rating | 320 ekW |
Emissions/Fuel Strategy | Low Fuel, Tier 2, Tier 3, EU Stage IIIA |
Voltage | 208 to 600 Volts |
Frequency | 60 Hz |
Speed | 1800 RPM |
Duty Cycle | Standby, Prime |
Engine Specifications
+ -Engine Model | C15 ATAAC, I-6, 4-Stroke Water-Cooled Diesel |
Bore | 5.4in |
Stroke | 6.75in |
Displacement | 927.56in³ |
Compression Ratio | 16.1:1 |
Aspiration | Air to Air Aftercooled |
Fuel System | MEUI |
Governor Type | Adem™A4 |
Generator Set Dimensions
+ -Length - Maximum | 168.2in |
Width - Maximum | 81in |
Height - Maximum | 126.3in |
Standard Equipment:
Air Inlet
+ --
Air cleaner
Air System
+ --
Turbocharger
-
Air cleaner - Non canister disposable paper filter
-
Aftercooler core
Control Panel
+ --
GCCP 1.3
-
GCCP 1.3 Genset Controller
Cooling
+ --
Package mounted radiator
Cooling System
+ --
Caterpillar extended life coolant
-
Fan drive, battery charging alternator drive
-
Radiator and cooling fan with guard
-
Coolant drain line with valve
Exhaust
+ --
Base, formed steel with single wall integral 8-hour fuel tank
-
Standard open set fuel tank/base supplied
-
Exhaust flange outlet
Fuel
+ --
Secondary fuel filters
-
Primary fuel filter with integral water separator
-
Fuel priming pump
Fuel System
+ --
Primary fuel filter w/integral water separator and secondary filter
-
Fuel priming pump
-
Engine fuel transfer pump
-
Flexible fuel lines
-
Fuel cooler
Generator
+ --
Matched to the performance and output characteristics of Cat engines
-
Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
-
IP23 Protection
Power Termination
+ --
Busbar
Generator And Attachments
+ --
Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
-
Integrated voltage regulator (IVR)
-
Segregated low voltage (AC/DC) wiring panel
-
Optional LC Frame generator - IP23 Protection
-
Power center, IP22
-
A Frame generator - IP21 Protection
Mounting
+ --
Rubber vibration isolators
Governing System
+ --
Cat electronic governor (ADEM A4).
Lube System
+ --
Oil cooler
-
Oil drain valves
Mounting System
+ --
Captive linear vibration isolators between base and engine-generator includes lifting provisions and termination points for coolant and lube oil drain lines
Starting/charging
+ --
24 Volt battery with rack and cables
-
24 volt starting motor
-
Batteries
General
+ --
Engine and alternator pre paint, Caterpillar yellow
-
Paint - Caterpillar yellow except rails and radiators gloss black
Optional Equipment:
Air Inlet System
+ -Single element air cleaner
Dual element air cleaner
Exhaust
+ -Industrial, residential, critical mufflers
Certifications
+ -EU Certificate of Conformance (CE)
Global certification for CIS
Circuit Breakers
+ -Shunt trip for IEC circuit breaker
Padlockable circuit breaker device
4 Pole (IEC-100% rated) Circuit breakers - Motorised
Auxiliary contacts, circuit breaker
3 Pole (IEC-100% rated) Circuit breakers - Motorised
3 Pole (IEC-100% rated) Circuit breakers - Package mounted
4 Pole (IEC-100% rated) Circuit breakers - Package mounted
Power terminal strip
Generator
+ -Oversize and premium generators
Anti-condensation heater
Excitation: [ ] Permanent magnet excitation (PMG) Excited (PM) [ ] Internally Excited (IE)
Power Termination
+ -Circuit breakers, UL listed
Circuit breakers, IEC compliant
Control Panels
+ -GCCP 1.4
Volt free contacts
Local annunciator
Remote annunciator module
Local alarm horn
Oil temperature displays
Protective devices: Earth fault relay ; Earth leakage Ground fault relay ; Overload shutdown via breaker ; Low fuel level alarm ; Low fuel level shutdown ; High fuel level alarm ; Fuel level sensor
Starting/charging
+ -Jacket water heater
Charging alternator
Heavy duty starting system
Battery chargers
Oversize batteries
Cooling System
+ -Stone guards
Radiator duct flange
Low coolant temperature alarm
Enclosures
+ -Sound attenuated enclosures
High ambient sound attenuated enclosures
General
+ -Sound attenuated, weather protective or high ambient weather protective enclosure
CSA Certification
Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
EEC Declaration of Conformity
Integral & sub-base UL listed dual wall fuel tanks
Automatic transfer switches (ATS)
Single or dual wall sub-base fuel tanks
The following options are based on regional and product configuration:
EU Certificate of Conformance (CE)
Single or dual wall integral fuel tanks
Narrow, wide or skid base
UL 2200 package
Exhaust System
+ -Engine mounted muffler
End in/end out mufflers - 10, 25 and 35 dBA attenuation
6 and 8 inch elbow kit
Manifold and turbocharger guards
Flexible exhaust fittings
6 and 8 inch flange GP
Fuel System
+ -Manual fuel transfer pump
Dual wall fuel tank base
Fuel transfer system controls
Generator And Attachments
+ -Space heaters
Permanent magnet excitation (PMG) generator
Ingress protection
LC frame generator
Oversize A Frame generator
LC frame CIP generator
CIP A Frame generator
Oversize LC frame generator
Lube System
+ -Manual sump pump
Mounting System
+ -Narrow skid base - replaces standard fuel tank base
Special Test / Reports
+ -PGS Test report @ 1.0 power factor
PGS Test report @ 0.8 power factor
Starting / Charging System
+ -5 Amp single Battery charger
Battery disconnect switch
Jacket water heater