Generator Set Specifications
+ -Maximum Rating | 330 kVA |
Minimum Rating | 230 kVA |
Emissions/Fuel Strategy | EU Stage IIIA |
Voltage | 200 to 400 Volts |
Frequency | 50 Hz |
Speed | 1500 rpm |
Duty Cycle | Standby, Prime |
Engine Specifications
+ -Engine Model | C9 ATAAC, I-6, 4-Stroke Water-Cooled Diesel |
Bore | 4.41in |
Stroke | 5.87in |
Displacement | 537.01in³ |
Compression Ratio | 16.1:1 |
Aspiration | Air to Air Aftercooled |
Fuel System | Hydraulic electronic unit injection |
Governor Type | Adem™A4 |
Generator Set Dimensions
+ -Length - Maximum | 157in |
Width - Maximum | 47.5in |
Height - Maximum | 73.5in |
Standard Equipment:
Air Inlet System
+ --
Air cleaner, light duty with disposable paper filter
Control Panels
+ --
GCCP 1.3
Cooling System
+ --
Fan drive, battery charging alternator drive
-
Radiator and cooling fan with guard
-
Caterpillar extended life coolant
-
Coolant drain line with valve
Exhaust System
+ --
Stainless steel exhaust flex, gaskets, rain cap & SAE exhaust flange for customer use - shipped loose
Fuel System
+ --
Base, formed steel with single wall integral 8-hour fuel tank
-
Standard open set fuel tank/base supplied
Generators And Generator Attachments
+ --
12 Leads
-
Mandatory option circuit breaker, IEC, 3 pole mounted in power centre
-
Voltage regulator (single phase sensing)
-
Segregated low voltage (AC/DC) wiring panel
-
IP23 Protection
-
Power centre, IP22
Governing System
+ --
Cat electronic governor (ADEM A4)
Lube System
+ --
Oil drain valves
-
Lubricating oil
-
Oil cooler
Mounting System
+ --
Includes lifting provisions and termination points for coolant and lube oil drain lines
-
Captive linear vibration isolators between base and engine-generator
Starting / Charging System
+ --
24V battery with rack and cables
General
+ --
Engine and alternator re-paint, Caterpillar yellow
Optional Equipment:
Certifications
+ -European Certificate for Conformance
Global Certification for CIS
Air Inlet System
+ -Single element air cleaner
Circuit Breakers
+ -4 Pole (IEC-100% rated) Circuit breaker upgrades: 400, 630, 800 and 100 amps
Control Panels
+ -Control panel protective devices: Earth fault relay ; Earth leakage ground fault ; overload shutdown via breaker ; Low fuel level shutdown ; Low fuel level alarm ; Fuel level sensor
Control panel Options: Volt free contacts ; Local alarm horn ; Oil temperature displays
Cooling System
+ -Radiator duct flange
Low coolant temperature alarm
Enclosures
+ -Sound attenuated enclosure
High ambient sound attenuated enclosure
Exhaust System
+ -5 and 6 inch elbow kits
5 - 6 inch flange adaptor
Mufflers - End in/end out; 10 dBA or 25 dBA attenuation
6 inch flange
Fuel System
+ -Integral dual wall fuel tank base
Generators And Attachments
+ -Permanent magnet excitation (PMG) generator
Oversize, AREP, CIP generators
Mounting System
+ -Narrow skid base
Starting / Charging System
+ -Jacket water heater
5 Amp single Battery charger
Battery disconnet switch