D250 GC (60 Hz) Generator Set
At a Glance
Maximum Rating
250 ekW
|
Minimum Rating
250 ekW
|
Emissions/Fuel Strategy
EPA Stationary Emergency
|
Voltage
208 to 600 Volts
|
Request a Quote
Overview
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Generator Set Specifications
+
-
Maximum Rating |
250 ekW |
Minimum Rating |
250 ekW |
Emissions/Fuel Strategy |
EPA Stationary Emergency |
Voltage |
208 to 600 Volts |
Frequency |
60 Hz |
Speed |
1800 rpm |
Duty Cycle |
Standby |
Engine Specifications
+
-
Engine Model |
Cat® C9 In-line 6, 4-cycle Diesel |
Bore |
4.4in |
Stroke |
5.9in |
Displacement |
538in³ |
Compression Ratio |
16.3:1 |
Aspiration |
Turbocharged Air-to-Air Aftercooled |
Fuel System |
HEUI |
Governor Type |
Adem™A4 |
Generator Set Dimensions
+
-
Length - Maximum |
155.5in |
Width - Minimum |
56.3in |
Width - Maximum |
56.7in |
Height - Minimum |
67.2in |
Height - Maximum |
86.7in |
Dry Weight - Genset (minimum) |
5324.2lb |
Dry Weight - Genset (maximum) |
6735.1lb |
Standard Equipment:
Air Inlet System
+
-
-
Air cleaner - Non-Canister, Disposable
-
Aftercooler core
-
Turbocharger
Cooling System
+
-
-
Jacket water pump, gear driven, centrifugal
-
Radiator sight gauge
-
Blower fan and fan drive with guards
-
Thermostats and housing.
-
Coolant drain valve.
-
Radiator, Package mounted.
Fuel System
+
-
-
Fuel priming pump
-
Engine fuel transfer pump
-
Primary fuel filter w/integral water separator and secondary filter, spin on
-
Integral Tank Base, 24 Hrs, UL142
Generator Set
+
-
-
Factory tested to design specifications at full load conditions
-
Complete system designed & built at ISO 9001:2000 certified facilities
-
All protective devices and control functions simulated and checked
Generators And Generator Attachments
+
-
-
Easy access to AVR and terminals
-
Insulation, Class H
-
Brushless, self-excited 2/3 pitch (600V uses Internal Excitation)
-
Voltage regulator (single phase sensing)
-
Terminal Box, IP22 RHS Facing, Bottom Cable Entry
-
12 Leads
-
Standard winding protection for non-harsh environments with relative humidity ? 95%
-
IP23 protection
Governing System
+
-
-
Cat Electronic Governor (ADEM A4)
Lube System
+
-
-
Oil filler and dipstick.
-
Lubricating Oil, CK-4 (10W-30)
-
Shallow oil pan.
-
Oil filter, spin on.
-
Fumes disposal to front of radiator.
-
Oil cooler
-
Oil drain with valve.
Mounting System
+
-
-
Includes lifting provisions and termination points for coolant and lube oil drain lines
-
Captive linear vibration isolators between base and engine-generator
Protection
+
-
-
Safety Shutoff - Overspeed
-
Safety Shutoff - High water temperature
-
Safety Shutoff - Low Oil Pressure
Starting/charging System
+
-
-
24-volt electric starting motor.
-
24V, 45 amp charging alternator.
General
+
-
-
Vibration damper.
-
Lifting Eyes
-
Parts Book
Optional Equipment:
Air Inlet System
+
-
Air Cleaner (Non-Canister Disposable)
Bases, Mounting & Fuel Tanks
+
-
Integral Tank Base, 24 Hrs, UL142
Audio & Visual Fuel Alarm (@90% Fuel Level)
Wide Base - Skid
Fuel Tank Fill Pipe & Lockable Cap
Circuit Breaker
+
-
400A LS/I
600A LS/I
1200A LSI
600A LSI
1200A LS/I
Auxiliary Contacts
400A LSI
800A LSI
800A LS/I
Control System
+
-
Twist Release, Red Button Emergency Stop
Product Link Remote Monitoring hardware
16 -light NFPA 99/110 Annunciator
Volt Free Contacts
Ground Fault Relay
20A GFCI (Ground Fault Circuit Interrupter)
Audible Alarm Gp
100A Load Center
Enclosures
+
-
E-Stop
AC & DC Source Lights
Sound Attenuated Level 2 Enclosure (White)
Exhaust System
+
-
6" Muffler - 25 dBA Attenuation
Flexible Exhaust Connection
Manifold & Turbocharger Guards
Generator
+
-
Permanent Magnet Generator
Space Heater
Starting System
+
-
Standard Battery Set: 1000 CCA, 90 amp/hr.
Battery Charger (UL Certified)
Jacket Water Heater
General
+
-
CSA Certification
Extended Service Coverage
Generator Test Report
UL2200 Certification