D300 GC (60 Hz) Generator Set
At a Glance
Minimum Rating 300 ekW |
Maximum Rating 300 ekW |
Emissions/Fuel Strategy EPA Stationary Emergency |
Voltage 208 to 600 Volts |
Request a Quote Overview
Generator Set Specifications
+ -Minimum Rating | 300 ekW |
Maximum Rating | 300 ekW |
Emissions/Fuel Strategy | EPA Stationary Emergency |
Voltage | 208 to 600 Volts |
Frequency | 60 Hz |
Speed | 1800 rpm |
Duty Cycle | Standby |
Engine Specifications
+ -Engine Model | Cat® C9 In-line 6, 4-cycle diesel |
Bore | 4.4in |
Stroke | 5.9in |
Displacement | 538in³ |
Compression Ratio | 16.3:1 |
Aspiration | Turbocharged Air-to-Air Aftercooled |
Fuel System | HEUI |
Governor Type | Adem™A4 |
Generator Set Dimensions
+ -Length - Maximum | 155.5in |
Width - Minimum | 56.3in |
Width - Maximum | 56.7in |
Height - Minimum | 67.2in |
Height - Maximum | 86.7in |
Dry Weight - Genset (minimum) | 5518.2lb |
Dry Weight - Genset (maximum) | 6929.1lb |
Standard Equipment:
Air Inlet System
+ -Aftercooler core
Turbocharger
Air cleaner - Non-Canister, Disposable
Cooling System
+ -Jacket water pump, gear driven, centrifugal
Thermostats and housing.
Coolant drain valve.
Radiator sight gauge
Blower fan and fan drive with guards
Radiator, Package mounted.
Fuel System
+ -Integral Tank Base, 24 Hrs, UL142
Fuel priming pump
Engine fuel transfer pump
Primary fuel filter w/integral water separator and secondary filter, spin on
Generator Set
+ -Complete system designed & built at ISO 9001:2000 certified facilities
All protective devices and control functions simulated and checked
Factory tested to design specifications at full load conditions
Generators And Generator Attachments
+ -IP23 protection
12 leads
Insulation, Class H
Standard winding protection for non-harsh environments with relative humidity ? 95%
Voltage regulator (single phase sensing)
Easy access to AVR and terminals
Terminal Box, IP22 RHS Facing, Bottom Cable Entry
Brushless, self-excited 2/3 pitch (600V uses Internal Excitation)
Governing System
+ -Cat Electronic Governor (ADEM A4)
Lube System
+ -Shallow oil pan.
Oil cooler
Fumes disposal to front of radiator.
Oil drain with valve.
Oil filler and dipstick.
Oil filter, spin on.
Lubricating Oil, CK-4 (10W-30)
Mounting System
+ -Captive linear vibration isolators between base and engine-generator
Includes lifting provisions and termination points for coolant and lube oil drain lines
Protection
+ -Safety Shutoff - High water temperature
Safety Shutoff - Low Oil Pressure
Safety Shutoff - Overspeed
Starting/charging System
+ -24-volt electric starting motor.
24V, 45 amp charging alternator.
General
+ -Lifting Eyes
Vibration damper.
Parts Book
Optional Equipment:
Air Inlet System
+ -Air Cleaner (Non-Canister Disposable)
Bases, Mounting & Fuel Tanks
+ -Integral Tank Base, 24 Hrs, UL142
Audio & Visual Fuel Alarm (@90% Fuel Level)
Wide Base - Skid
Fuel Tank Fill Pipe & Lockable Cap
Circuit Breaker
+ -400A LSI
600A LSI
1200A LSI
800A LS/I
Auxiliary Contacts
600A LS/I
1200A LS/I
400A LS/I
800A LSI
Control System
+ -Audible Alarm Gp
16 -light NFPA 99/110 Annunciator
Twist Release, Red Button Emergency Stop
Ground Fault Relay
100A Load Center
Product Link Remote Monitoring hardware
20A GFCI (Ground Fault Circuit Interrupter)
Volt Free Contacts
Enclosures
+ -Sound Attenuated Level 2 Enclosure (White)
AC & DC Source Lights
E-Stop
Exhaust System
+ -6" Muffler - 25 dBA Attenuation
Manifold & Turbocharger Guards
Flexible Exhaust Connection
Generator
+ -Space Heater
Permanent Magnet Generator
Starting System
+ -Battery Charger (UL Certified)
Jacket Water Heater
Standard Battery Set: 1000 CCA, 90 amp/hr.
General
+ -CSA Certification
Extended Service Coverage
UL2200 Certification
Generator Test Report