DE400 GC Generator Set
360° Exterior View
At a Glance
|
|
|
|
Overview
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Generator Set Specifications
+ -Maximum Rating | 400 kVA |
Minimum Rating | 400 kVA |
Emissions/Fuel Strategy | Non-Certified Emissions |
Voltage | 380 to 415 Volts |
Frequency | 50 Hz |
Speed | 1500 rpm |
Duty Cycle | Standby |
Engine Specifications
+ -Engine Model | C9.3B, I-6, 4-cycle diesel |
Bore | 4.53in |
Stroke | 5.87in |
Displacement | 567.5in³ |
Compression Ratio | 16.5:1 |
Aspiration | Turbocharged Air-to-Air Aftercooled |
Fuel System | Common Rail |
Governor Type | ADEM™A6 |
Generator Set Dimensions
+ -Length - Maximum | 104.8in |
Width - Maximum | 44in |
Height - Maximum | 69.5in |
Dry Weight - Genset (maximum) | 5070.6lb |
Standard Equipment:
Engine
+ --
C9.3B, Inline 6 cylinder, 4 stroke diesel
Air, Cooling & Exhaust
+ --
Standard air filter
Genset Control
+ --
GCCP 1.1
Governor
+ --
Adem A4
Alternator
+ --
A Frame standard alternator
Fuel Storage
+ --
Single wall 8 hour fuel tank
General
+ --
Engine and alternator pre-paint, Caterpillar yellow
Optional Equipment:
Air, Cooling & Exhaust
+ -6" Elbow kit
Dual element air filter
5-6" Exhaust adapter
Canopy silencer
5" Elbow kit
6" Elbow kit
6" Muffler - 25 dBA attenuation
5" Muffler - 10 dBA Attenuation
Single stage air filter
No muffler
Alternator Requirements
+ -IP Standard @ 21 FUW A-Frame
Space heater
Auxiliary Supply Voltage
+ -240V
Certification
+ -Australia, CIS, Gulf Certification
Certificate of Conformance 13
Circuit Breaker
+ -3 Pole Circuit breaker 800A
Circuit breaker padlock
4 Pole Circuit breaker 630A
4 Pole Circuit breaker 1250A
3 Pole Circuit breaker 630A
4 Pole Circuit breaker 800A
Overload via alarm switch on breaker
Neutral earth link
3 Pole Circuit breaker 1250A
Auxiliary contacts
Shunt Trip
Enclosure
+ -Cat GC enclosure
Fuel Storage
+ -Low fuel level shutdown
Fuel level alarms
Low fuel level alarm
Single wall tank with containment 01
High fuel level alarm
Dual wall 8 hour fuel tank
Genset Control
+ -PLG Cellular 4G E
Oil temperature displays
Coolant heater
Battery charger
Standby Pack (Smart Jacket water heater, Battery charger)
PLG Cellular 4G U
Voltage adjust potentiometer
Low coolant temperature alarm
Speed adjust potentiometer
PLG Ethernet
Battery