DG200-2 (3 phase)
At a Glance
|
|
|
|
Overview
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Generator Set Specifications
+ -Frequency | 60 Hz |
Natural Gas Rating | 200 eKW |
Emissions/Fuel Strategy | U.S. EPA Certified for Stationary Emergency Application |
Displacement | 864.71in |
Fuel Type | Natural Gas |
Speed | 1800 rpm |
Engine Specifications
+ -Engine Model | 14.2 L, Inline 6, 4 Cycle, Spark - Ignited |
Fuel System | Carburetor, Down Draft |
Aspiration | Turbocharged-Aftercooled |
Governor Type | Electronic |
Compression Ratio | 9.5:1 |
Bore | 5.31in |
Stroke | 6.5in |
Generator Set Dimensions
+ -Length | 127.95in |
Width | 52.93in |
Height | 67.37in |
Weight | 5756lb |
Standard Equipment:
Cooling
+ --
Closed coolant recovery system
-
Factory-installed radiator
-
50/50 Ethylene glycol antifreeze
-
Radiator and cooling fan complete with protective guards
-
Standard ambient temperatures up to 50°C (122°F)
Air Inlet
+ --
Single element air filter
Fuel
+ --
Primary and secondary fuel shut-off
-
Low fuel pressure switch
-
Fuel pressure test po
-
Natural Gas or LP Vapor
-
NPT connection
-
Dual lock off valves
Exhaust
+ --
Exhaust outlet with 3” pipe
Generator
+ --
Permanent magnet excitation
-
Full load capacity alternator
-
Class H insulation material
-
Permanent magnet excitation
-
Integrated Voltage Regulator
-
Matched to the performance and output characteristics of Cat engines
-
Class H insulation material
-
Full load capacity alternator
-
IP23 Protection
Controls
+ --
EMCP 4.2 Series generator set controller
Mounting
+ --
Vibration isolaton (puck type)
-
Rubber vibration isolators
Electric Power - Package Serial Number Prefix
+ --
Battery charging alternator
Electric Starting And/or Prelube
+ --
Battery cables
-
Solenoid activated starter motor
-
Engine electrical system
-
Solenoid activated starter motor
Governor
+ --
Electronic governor (non adjustable)
Control Panel
+ --
EMCP 4.2 Series generator set controller
Starting/charging
+ --
Batteries with rack and cables
-
12 volt starting motor
Optional Equipment:
Starting/charging
+ -Jacket water heater
Battery heater
Charging alternator
Battery charger – UL Listed 10 amp
General
+ -Enclosures: sound attenuated, weather protective
Suitable for Use as Service Equipment (SUSE)
Automatic transfer switches (ATS)
UL 2200 package
CSA Certification
Generator
+ -Thermal magnetic or electronic trip MCCBs
Anti-condensation heater
Shunt trip and auxiliary contact breaker
Anti-condensation heater
Excitation: [ ] Permanent Magnet Excited (PM)
Oversize and premium generators