G3512 1000kW Gas Generator Set
At a Glance
Gas Standby Rating
1000 ekW @ 0.8pf
|
Fuel Type
Natural Gas
|
Emissions/Fuel Strategy
U.S. EPA Certified for Non-Emergency Stationary Genset
|
RPM
1800 rpm
|
Request a Quote
Overview
Generator Set Specifications
+
-
Gas Standby Rating |
1000 ekW @ 0.8pf |
Fuel Type |
Natural Gas |
Emissions/Fuel Strategy |
U.S. EPA Certified for Non-Emergency Stationary Genset |
RPM |
1800 rpm |
Frequency |
60 Hz |
Compression Ratio |
9.7 |
Displacement |
3173in³ |
Engine Specifications
+
-
Engine Model |
G3512 |
Displacement |
3173in³ |
Aspiration |
TA |
Bore |
6.7in |
Stroke |
7.5in |
Generator Set Dimensions
+
-
Length |
205.7in |
Width |
90in |
Height |
99.4in |
Weight |
27500lb |
Standard Equipment:
Air Inlet
+
-
-
Two-element single-stage air cleaner with enclosure and service indicator
-
Dual air cleaners, 1 per side, with service indicator
Cooling System
+
-
-
Engine driven pumps for jacket water and separate circuit aftercooler
Cooling
+
-
-
Package mounted radiator
-
Jacket water and SCAC engine-driven pumps
-
Jacket water and SCAC thermostats
-
LH or RG connections when radiator is not selected
Exhaust
+
-
-
Dry exhaust manifolds, insulated and shielded
-
Individual exhaust port and turbocharger outlet wired to integrated temperature sensing module (ITSM) with GCEM providing alarms and shutdowns
-
Cat-flanged face outlet on turbocharger
Fuel
+
-
-
NOx sensor based air-fuel-ratio control
-
Pipeline Natural Gas: 800-1000 BTU/scf and 70-100 Methane Number
-
Gas Train: NFPA37 and CSA B149.3
-
0.5 to 5 psi engine fuel inlet pressure
Fuel System
+
-
-
Fuel system is sized for 31.5 to 47.2 MJ/NM3 dry pipeline natural gas with pressure of 10.2 to 34.5KPa to the engine fuel control valve
-
Engine-installed electronic control valve
-
Throttle plate, 24V DC actuator, controlled by GECM
-
24V DC energized-to-run (ETR) gas shutoff valve
-
Gas pressure regulator
General
+
-
-
Operation and maintenance manuals
-
Paint- Caterpillar Yellow except rails and radiators gloss black
-
Parts book
-
“Stationary Use Only” Label in Correspondence with EPA Nonroad Mobile SI rule
-
RH Service
-
Crankshaft vibration damper and guard
Lubrication
+
-
-
Cartridge style oil filter
-
Gear type lube oil pump
Starting/charging
+
-
-
Jacket water heater
-
Battery with cables and rack (shipped loose)
-
Electric Starter
-
Batteries with rack and cables
-
24V DC starting motors
Generator
+
-
-
NEMA Class H insulation
-
Permanent Magnet Excitiation
-
SR5
-
Anti-condensation space heater
-
Caterpillar's Digital Voltage Regulator (CDVR) including reactive droop capability, 3-phase voltage sensing, KVAR/PF modes, RFI suppression, and a min/max exciter
-
Winding temperature detectors
Ignition System
+
-
-
Electronic Ignition System (controlled by ADEM A4)
-
Individual Cylinder Detonation Sensitive Timing (DST)
Governing
+
-
-
ADEM A4 speed governor with 4 to 20ma (0V to 5V) speed input
Optional Equipment:
Air Inlet
+
-
Mounting brackets and piping
Air cleaner with precleaner
Control Panel
+
-
Local PC monitoring
Engine failure relay
Remote PC monitoring
Local alarm module
Remote annunciator
Cooling
+
-
Remote radiator for JW and SCAC circuits, level switch included but not wired
Inlet/Outlet connections
Coolant level drain line with valves, fan with guard
Circuit Breakers
+
-
2000A 3 Pole, UL-100% Rated Masterpact Circuit Breakers
Frame mounting
S LSI, G LSIG, P LSIG-P, 4th Digit Type
Right, left, rear mounted
1600A, 2000A 3 Pole, UL-100% Rated R-Frame Circuit Breakers
100% rated, 3-pole (UL/CSA/IEC) 5th Digit Rating
3-pole (IEC 947-2 rated)
1200A, 3 Pole, UL-100% Rated P-Frame Circuit Breakers
Exhaust
+
-
305 mm (12 in.) flange
Flexible fittings
18, 25 dBA Attenuation
305 mm (12 in.) muffler
305mm (12 in) spark arresting muffler
305 mm (12in.) elbow
Fuel System
+
-
3, 0-100 kPag, 4-20mA gas train pressure sensors
General
+
-
US AID emblem
Special paint order
Digital diagnostic tool
Tool set
Generator
+
-
Generator air filter
European bus bars
Low voltage extension box
Cable access box
Bearing temperature detectors
Starting/charging
+
-
20A, 24VDC battery charger
24V starting motors
45A, 24V charging alternator (requires engine driven pumps)