Gas Generator G3512H
360° Exterior View
360° Exterior View
At a Glance
|
|
|
|
Overview
G3512H Generator Set
Generator Set Specifications
+ -Continuous Rating | 1515 ekW / 1505 ekW @1.0pf |
Fuel Type | Natural Gas, Hydrogen Blend (up to 25%) |
Maximum Electrical Efficiency | 44.90% |
Frequency | 50 / 60 Hz |
RPM | 1500 rpm |
Engine Specifications
+ -Engine Model | G3512H |
Displacement | 3574in³ |
Aspiration | TA |
Bore | 6.7in |
Stroke | 8.5in |
Governor Type | ADEM A4 |
Generator Set Dimensions
+ -Length | 223in |
Width | 76in |
Height | 91in |
Dry Weight - Genset | 31085lb |
Standard Equipment:
Air Inlet
+ --
Package Mounted Air Cleaner with service indicator
Cooling
+ --
Jacket water and SCAC thermostats
-
2nd Stage CAT Flange
-
ANSI Class 150 JW Connection
-
Engine driven pumps for jacket water and aftercooler cooling
Control Panels
+ --
Dedicated customer wiring terminals
Control Panel
+ --
EMCP4.3
Exhaust
+ --
Dry exhaust manifolds insulated and shielded
-
Center section cooled turbocharger with Cat flanged outlet
Generator
+ --
High efficiency low voltage Cat generator, permanent magnet excitation, digital regulation, IP23 water ingress protection, & form wound construction.
Starting/charging
+ --
Electric Starter
General
+ --
Paint - Caterpillar Yellow except rails and radiators gloss black
-
Crankshaft vibration damper and guard
Optional Equipment:
Air Inlet
+ -Mounting brackets and piping
Air cleaner with precleaner
Control Panels
+ -Remote annunciator
Circuit Breakers
+ -Frame mounting circuit breaker orientation
2500A 3-pole IEC rated circuit breakers
Rear Mounted Circuit Breaker
3000A/3200A/4000A UL100% Rated Masterpact circuit breaker (60 Hz only)
LSI Long-Time, LSI-P Long-Time, LSIG Long-Time, LSIG-P Long-Time,
Control Panel
+ -Language Options
Cable Shroud Location
Engine failure relay
Discrete I/O module, 12 digital points, 8 'Form C' relay
16 point/32 light annunciator with NFPA99-110/CSA282 configuration
Empty Upper Box Right/Left
Local Alarm module
Synchronization module
Cat Connect: Ethernet, satellite, or cell telematics
Local/Remote PC Monitorring
Right/Left/Rear Extension Box
Cooling
+ -Remote radiator for JW and SCAC circuits
220V (50Hz), 240V (60Hz), 480V (60Hz) JW heater
Exhaust
+ -Flexible fitting [305mm x 305mm (12in. X 12in.)] w/ 12 bolt-flanges
406mm (16in.) sparking-arresting muffler with companion flange
Exhaust expander [250mm-329mm (10in-12in)]
305mm (12 in.) flange
Muffler options
Elbow exhaust
Fuel System
+ -1/2" NPT gas train conduit connectors
3, 0-100kPag 4-20mA gas train pressure sensors
Fuel Filter
Gas knockdown regulators
General
+ -Digital Diagnostic tool
US Aid emblem
Generator
+ -Generator air filter
Manual voltage control
Cable access box
RTD Monitorring
Bearing temperature detectors
Governing System
+ -ADEM A4 4-20mA (0-5V) speed input
Starting/charging
+ -Battery with cables and rack
24V Starting motors
20A, 24VDC battery charger
45A, 24V charging alternator (requires engine driven pumps)
Jacket water heater
Grid Code Compliance
+ -60 Hz: USA
50 Hz: Germany, Great Britain, Belgium, Romania, Italy, Ireland, Poland, Netherlands, Spain, France, and European Standard