Menu
View Details

Tap to Call

Cat EGP Switchgear

Cat EGP Switchgear

At a Glance

Configuration
Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications
Modes of Operation
Multi-unit Island and multi-unit standby mode with optional redundant controls and components.
Application
LV and MV (208V - 38 kV)
ANSI Protective Devices
15/25, 27/59, 81 O/U, 32, 40, 50, 51
Get More Information

Overview

EGP (Emergency Generator Paralleling) switchgear is used for paralleling multiple generators that are not directly connected to a utility source.

Expand All +

Technical Summary

+ -
Configuration Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications
Modes of Operation Multi-unit Island and multi-unit standby mode with optional redundant controls and components.
Application LV and MV (208V - 38 kV)

Generator Protective Devices

+ -
ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 50, 51

Environmental Parameters

+ -
Certifications IBC, CBC, UBC & OSHPD Certified
Control Panel Enclosure NEMA 1 or NEMA 3R Freestanding Construction
Operating Temperature 0°C to 50°C
Storage Temperature -20°C to +60°C
Low Voltage Standards NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
*This estimate is for the base rental charge only. Other fees and charges may apply and will be calculated at the time of rental. Does not include delivery fees.
*Images are for general reference only. Individual product models may vary. Please consult with your dealer to verify machine configuration.